    Fluke 376 FC 1000A AC/DC TRMS Wireless Clamp Meter with iFlexPowerpro company Limited is the distributor, supplier and service provider of ( Test Equipment Product Sales, Test Equipment Calibration, Test Equipment Rentals and Product Training) in Nigeria. Product overview: Fluke 376 FC True-RMS Clamp Meter with iFlex The Fluke 376...



    Add to quote

    Fluke 376 FC 1000A AC/DC TRMS Wireless Clamp Meter with iFlex

    Powerpro company Limited is the distributor, supplier and service provider of ( Test Equipment Product Sales, Test Equipment Calibration, Test Equipment Rentals and Product Training) in Nigeria.

    Product overview: Fluke 376 FC True-RMS Clamp Meter with iFlex

    The Fluke 376 FC True-rms Clamp Meter with iFlex is the most advanced troubleshooting tool for industrial and commercial electricians. The 376 is part of the Fluke Connect family of wireless test tools that enable you to log, trend and monitor measurements while remaining safely away from the arc flash zone through Bluetooth connectivity.

    Find the cause of difficult problems

    The 376 FC clamp meter uses an integrated low-pass filter for accurate measurements of non-linear signals, such as adjustable speed drives, electronic ballasts and other non-linear loads. The clamp also uses proprietary inrush measurement technology to filter out noise and capture motor starting current exactly as the circuit protection sees it.

    Measure:

    • Voltage to 1000 V AC or DC
    • Resistance to 60 kΩ with continuity detection
    • Min, max, average, and inrush recording to capture variations automatically
    • 500 mV DC measurement range to interface with other accessories
    • 1000 μF capacitance measurement

    Work safely and conveniently

    The 376 FC clamp carries a CAT III 1000 V, CAT IV 600 V safety rating, designed to offer you the highest possible protection in a test tool.

    The included iFlex flexible current probe provides easier access to large conductors in tight spaces. The flexible probe:

    • Expands the measurement range to 2500 A AC
    • Allows frequency measurement to 500 Hz with body jaw and iFlex

    Specifications: Fluke 376 FC True-RMS Clamp Meter with iFlex

    General Specifications
    AC Current via Jaw
    Range 999.9 A
    Resolution  0.1 A
    Accuracy  2% ±5 digits (10 Hz to 100 Hz)
    2.5% ±5 digits (100-500 Hz)
    Crest Factor (50 Hz/60 Hz) 3 @ 500 A
    2.5 @ 600 A
    Add 2% for C.F. >2
    AC Current via Flexible Current Probe
    Range 2500 A
    Resolution 0.1 A (≤ 600 A)
    1 A (≤ 2500 A)
    Accuracy 3% ±5 digits (5 – 500 Hz)
    Crest Factor (50/60Hz) 3.0 at 1100 A
    2.5 at 1400 A
    1.42 at 2500 A
    Add 2% for C.F. > 2
    Position Sensitivity
    Flexible current probe
      i2500-10 Flex i2500-18 Flex
    A    
    Distance from Optimum 0.5 in (12.7 mm) 1.4 in (35.6 mm)
    Error ±0.5 % ±0.5 %
    B    
    Distance from Optimum 0.8 in (20.3 mm) 2.0 in (50.8 mm)
    Error ±1.0 % ±1.0 %
    C    
    Distance from Optimum 1.4 in (35.6 mm) 2.5 in (63.5 mm)
    Error ±2.0 % ±2.0 %
    Measurement uncertainty assumes centralized primary conductor at optimum position, no external electrical or magnetic field, and within operating temperature range.
    DC Current
    Range 999.9 A
    Resolution 0.1 A
    Accuracy 2% ±5 digits
    AC Voltage
    Range 1000 V
    Resolution 0.1 V (≤600.0 V)
    1 V (≤1000 V)
    Accuracy 1% ±5 digits (20 Hz to 500 Hz)
    DC Voltage
    Range 1000 V
    Resolution 0.1 V (≤600.0 V)
    1 V (≤1000 V)
    Accuracy 1% ±5 digits
    mV dc
    Range 500.0 mV
    Resolution 0.1 mV
    Accuracy 1% ±5 digits
    Frequency via Jaw
    Range 5.0 Hz to 500.0 Hz
    Resolution  0.1 Hz
    Accuracy  0.5% ±5 digits
    Trigger level  5 Hz to 10 Hz, ≥10 A
    10 Hz to 100 Hz, ≥5 A
    100 Hz to 500 Hz, ≥10 A
    Frequency via Flexible Current Probe
    Range 5.0 Hz to 500.0 Hz
    Resolution  0.1 Hz
    Accuracy  0.5% ±5 digits
    Trigger level  5 Hz to 20 Hz, ≥25 A
    20 Hz to 100 Hz, ≥20 A
    100 Hz to 500 Hz, ≥25 A
    Resistance
    Range 60 kΩ
    Resolution 0.1 Ω (≤600 Ω)
    1 Ω (≤6000 Ω)
    10 Ω (≤60 kΩ)
    Accuracy 1% ±5 digits
    Capacitance
    Range 1000 μF
    Resolution 0.1 μF (≤ 100 μF)
    1 μ F (≤ 1000 μF)
    Accuracy 1% ±4 digits
    Mechanical Specifications
    Maximum voltage between any terminal and earth ground 1000 V
    Batteries 2 AA, NEDA 15A, IEC LR6
    Operating temperature -10 °C to +50 °C
    Storage temperature -40 °C to +60 °C
    Operating humidity -
    non-condensing (< 10°C)
    ≤90% RH (at 10 °C to 30 °C)
    ≤75% RH (at 30 °C to 40 °C)
    ≤45% RH (at 40 °C to 50 °C)
    Operating altitude 2000 m
    Storage altitude 12,000 m
    Size (L x W x H) 249 x 85 x 45 mm
    Weight 395 g
    Jaw opening 34 mm
    Flexible current probe diameter 7.5 mm
    Flexible current probe cable length
    (head to electronics connector)
    1.8 m
    Safety IEC 61010-1, Pollution Degree 2
    IEC 61010-2-032: CAT III 1000 V / CAT IV 600 V
    IEC 61010-2-033:CAT III 1000 V / CAT IV 600 V
    IP rating IEC 60529: IP30, non-operating
    Radio Frequency Certification FCC ID T68-FBLE IC:6627A-FBLE
    Electromagnetic Compatibility (EMC)
    International IEC 61326-1: Portable, Electromagnetic Environment, IEC 61326-2-2
    CISPR 11: Group 1, Class A
    Group 1: Equipment has intentionally generated and/or uses conductively-coupled radio frequency energy that is necessary for the internal function of the equipment itself.
    Class A: Equipment is suitable for use in all establishments other than domestic and those directly connected to a low-voltage power supply network that supplies buildings used for domestic purpose. There may be potential difficulties in ensuring electromagnetic compatibility in other environments due to conducted and radiated disturbances. Emissions that exceed the levels required by CISPR 11 can occur when the equipment is connected to a test object.
    Korea (KCC) Class A Equipment (Industrial Broadcasting & Communication Equipment)
    Class A: Equipment meets requirements for industrial electromagnetic wave equipment and the seller or user should take notice of it. This equipment is intended for use in business environments and not to be used in homes.
    USA (FCC) 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103.
    Temperature coefficients Add 0.1 x specified accuracy for each degree C above 28 °C or below 18 °C

    You can use this tab for adding shipping details, return policies and information or measurements etc.