    Fluke 1662 SCH Installation Tester w/mem SchukoPowerpro company Limited is the distributor, supplier and service provider of ( Test Equipment Product Sales, Test Equipment Calibration, Test Equipment Rentals and Product Training) in Nigeria. Product overview: Fluke 1662 Multifunction Testers Fluke 1662 Multifunction Installation Tester delivers solid, basic installation testing features...



    Add to quote

    Fluke 1662 SCH Installation Tester w/mem Schuko

    Powerpro company Limited is the distributor, supplier and service provider of ( Test Equipment Product Sales, Test Equipment Calibration, Test Equipment Rentals and Product Training) in Nigeria.

    Product overview: Fluke 1662 Multifunction Testers

    Fluke 1662 Multifunction Installation Tester delivers solid, basic installation testing features

    The Fluke 1662 installation tester gives you Fluke reliability and all the basic testing power you need for day-in, day-out installation testing. It tests to all local regulations and is easy and intuitive to use. Additional helpful features like the On/Off switchable auto-start for RCD and loop test, and self-test save time and give you more confidence in your results.

    • Measures RCD switching time and tripping level (ramp test)
    • Measures trip time and current for RCD type A & AC in one test
    • Measures RCD variable current
    • Provides automatic RCD test sequence
    • Includes Z-max memory for loop tests to support easy evaluation of the highest loop test value
    • Provides unique zero adapter for fast, reliable and accurate test lead and mains cord compensation
    • Includes a phase sequence indicator
    • Comes with hard carrying case, padded carrying and waist strap, and remote control probe and lead

    Key features

    A solid, reliable, basic installation tester

    • Tests voltage and frequency
    • Checks wiring polarity to detect broken N wires
    • Measures insulation resistance and loop and line resistance
    • Measures motor windings with continuity test
    • Calculates prospective earth fault current (PEFC/IK) and prospective short-circuit current (PSC/IK)

    Specifications: Fluke 1662 Multifunction Testers

    AC voltage measurement

    Range

    500 V

    Resolution

    0.1 V

    Accuracy 45 Hz – 66 Hz

    0.8% + 3

    Input impedance

    360 kΩ

    Overload protection

    660 V rms

    Continuity testing (RLO)

    Range (autoranging)

    20 Ω / 200 Ω / 2000 Ω

    Resolution

    0.01 Ω / 0.1 Ω / 1 Ω

    Open Circuit Voltage

    >4 V

    Insulation resistance measurement (RISO)

    Accuracy of tTest voltage (at rated test current)

    +10%, -0%

    Test voltage

    100 V
    250 V
    500 V
    1000 V

    Insulation resistance range

    20 MΩ / 50 MΩ
    20 MΩ / 100 MΩ
    20 MΩ / 200 MΩ
    20 MΩ / 200 MΩ / 500 MΩ
    20 MΩ / 200 MΩ / 1000 MΩ

    Resolution

    0.01 MΩ / 0.1 MΩ
    0.01 MΩ / 0.1 MΩ
    0.01 MΩ / 0.1 MΩ
    0.01 MΩ / 0.1 MΩ / 1 MΩ
    0.01 MΩ / 0.1 MΩ / 1 MΩ

    Test current

    1 mA @ 50 kΩ
    1 mA @ 100 kΩ
    1 mA @ 250 kΩ
    1 mA @ 500 kΩ
    1 mA @ 1 MΩ

    Loop and line impedance (ZI)

    Range

    10 Ω / 0.001 Ω / High current mΩ mode

    Resolution

    0.01 Ω / 0.1 Ω / 1 Ω

    Prospective earth fault current, PSC test

    Range

    1000 A / 10 kA (50 kA)

    Resolution

    1 A / 0.1 kA

    Computation

    Prospective earth fault current (PEFC) or Prospective short circuit current (PSC) determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance, respectively.

    RCD testing, RCD types tested

    RCD Type

    A4, AC¹, G², S³

    Notes

    ¹Responds to AC
    ²General, no delay
    ³Time delay
    4Responds to pulsed signal
    5Responds to smooth DC signal

    Tripping speed test (ΔT)

    Current settings¹

    10-30-100-300-500-1000 mA – VAR
    10-30-100 mA

    Multiplier

    x ½, x 1
    x 5

    Measurement range

    RCD Type G

    310 ms
    50 ms

    RCD Type S

    510 ms
    160 ms

    Notes

    ¹1000 mA type AC only
    700 mA maximum type A in VAR mode
    VAR mode not available for type B.

    RCD/FI-Tripping Current Measurement/Ramp Test (IΔN)

    Current range

    30% to 110% of RCD rated current¹

    Step size

    10% of IΔN²

    Dwell time

    Type G

    300 ms/step

    Type S

    500 ms/step

    Measurement accuracy

    ±5%

    Specified trip current ranges (EN 61008-1)

    50% to 100% for Type AC
    35% to 140% for Type A (>10 mA)
    35% to 200% for Type A (≤10 mA)
    50% to 200% for Type B
    ²5% for Type B

    Notes

    ¹30% to 150% for Type A IΔN > 10 mA
    30% to 210% for Type A IΔN = 10 mA
    20% to 210% for Type B

    Phase Sequence Indication

    Icon

     Phase Sequence indicator is active.

    General Specifications

    Size (L x W x H)

    10 x 25 x 12.5 cm

    Weight (incl. batteries)

    1.3 Kg

    Battery size, quantity

    Type AA, 6 ea.

    Sealing

    IP-40

    Safety

    Complies with EN61010-1 Ed 2.0 (2001-02), UL61010, ANSI/ISA –s82.02.01 2000 and CAN/CSA c22.2 No. 1010 2nd edition

    Overvoltage

    CAT III / 500V; CAT IV 300V

    Performance

    EN61557-1 to EN61557-7 Second Edition and EN61557-10 Second Edition

     

     